Voltage Drop Calculator
Enter the voltage, the load and the one-way length to get the voltage drop, the voltage at the load and the smallest wire size that keeps the drop within your target. Then price the wire and add it to an estimate.
- Drop in volts and percent
- Smallest wire size
- Copper or aluminum
- No email required
Circuit
Conductors
Enter the size you picked for ampacity. The NEC recommends no more than 3% on a branch circuit and 5% for the feeder and branch circuit together (informational notes to 210.19 and 215.2(A)(2), 2023 NEC). For a branch circuit off a feeder, use what is left of 5% after the feeder’s drop.
Wire for the estimate
Optional. Your price per foot is saved in this browser for each size and material.
Count every conductor of this size: two for a single-phase load, three for three phase, plus the neutral if it is the same size. The equipment ground is usually smaller, so price it on its own line. Makeup covers terminations, loops and waste; 10% is a typical starting point, not a rule.
Your estimate
Saved in this browser. Add rooms or runs from any of our calculators.
Nothing here yet. Run the numbers above and press “Add to estimate”.
Ready to send this as a proposal?
BuildWorkPro builds bids from line items like these, with your margin and overhead, and turns them into a PDF proposal. $79/mo flat, free for 14 days.
Start free trialHow it’s calculated
Voltage drop. Single phase: VD = 2 × K × I × L ÷ CM. Three phase: VD = √3 × K × I × L ÷ CM. I is the load current, L is the one-way length in feet and CM is the circular mils of one conductor times the number of parallel sets. The 2 counts the trip out and back. The drop in percent is VD ÷ system voltage × 100, and the voltage at the load is the system voltage minus VD.
K. The resistance of one circular-mil foot of conductor at 75 °C: 12.9 Ω for copper and 21.2 Ω for aluminum, the values Mike Holt gives for this formula. They match the DC resistance of stranded conductors at 75 °C, the temperature the NEC’s Chapter 9 resistance values are based on.
Circular mils. AWG sizes come from the gauge’s definition in ASTM B258: diameter = 0.005 in × 92(36 − n) ÷ 39, with n = 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0, and area in circular mils = the diameter in mils, squared. That makes 12 AWG 6,530 cmil, 10 AWG 10,383 and 4/0 211,600. A kcmil size is its own number: 250 kcmil is 250,000 cmil.
Smallest size. The calculator tries each size of the same material, smallest first, up to 500 kcmil, and shows the first one whose drop is within your target. It starts at 14 AWG for copper and 12 AWG for aluminum, the smallest sizes the NEC allows (310.3(A)), and at 1/0 when you run parallel sets (310.10(G)). The longest run is target % × voltage × CM ÷ (2 or √3 × K × I).
What it does not do. It does not size for ampacity. Pick the size from NEC 310.16 with the terminal temperature limits in 110.14(C) first, then check the run here. It uses DC resistance only, so it ignores reactance and power factor. That is close for 1/0 AWG and smaller. On 2/0 and larger, especially in steel conduit, check with AC impedance and the load’s power factor. If you upsize for voltage drop, a wire-type equipment grounding conductor goes up in proportion (250.122(B)).
The NEC recommendation. The informational notes to 210.19 (branch circuits) and 215.2(A)(2) (feeders) in the 2023 NEC recommend 3% on a branch circuit and 5% for feeder and branch circuit combined. Older editions put the same notes at 210.19(A) and 215.2(A)(1). Informational notes are not enforceable on their own (90.5(C)), but an energy code or a local amendment can make a limit mandatory.
Wire for the estimate. Footage = conductors per set × one-way length × parallel sets × (1 + makeup %), rounded up to the foot, for the size you entered or the size that meets your target. The size that meets your target is never smaller than the size you entered. It is priced at your price per foot for that size and material. Nothing is priced with numbers you did not enter.
Pricing the whole job? The electrical estimate template turns circuits into wire footage by cable type and openings into labor hours.
Keep going
More free tools and price data: Conduit Fill Calculator · Box Fill Calculator · Labor Burden Calculator · Copper Wire Prices
Frequently asked questions
What is the voltage drop on 100 ft of 12 AWG copper at 16 A and 120 V?
6.32 V, or 5.27% of 120 V, which leaves 113.7 V at the load. That is over the 3% the NEC informational note recommends for a branch circuit. 10 AWG brings it to 3.31%, still over, and 8 AWG to 2.08%. On 12 AWG at 16 A, the longest run that stays within 3% is 56 ft one way.
What size wire do I need for 150 ft at 30 A on 240 V single phase?
To stay within 3%, 8 AWG copper or 4 AWG aluminum. 10 AWG copper, the usual size for a 30 A circuit, drops 11.18 V over that run, 4.66%. 8 AWG copper drops 7.03 V, 2.93%. In aluminum, 6 AWG lands just over at 3.03%, so it takes 4 AWG at 1.9%. Size for ampacity first, then go up for voltage drop, and increase a wire-type equipment ground in proportion (NEC 250.122(B)).
Is voltage drop a code requirement?
Usually not under the NEC alone. The 3% branch-circuit and 5% combined figures are informational notes (2023 NEC 210.19 and 215.2(A)(2)), and 90.5(C) says informational notes are not enforceable. A few NEC rules do set mandatory limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps. Energy codes go further: the 2021 IECC (C405.10) limits the combined drop across customer-owned service, feeder and branch-circuit conductors to 5% in commercial buildings, and ASHRAE 90.1 has a similar 5% limit. Some states and cities amend the NEC to make the note a rule, and equipment instructions that set a minimum voltage are enforceable under 110.3(B). Ask your AHJ what applies to the job.
Does aluminum wire need to be bigger than copper for voltage drop?
Yes. Aluminum has about 64% more resistance than copper of the same size (K of 21.2 against 12.9), so it drops about 64% more voltage. On the 150 ft, 30 A, 240 V circuit, copper meets 3% at 8 AWG and aluminum at 4 AWG. To compare them on cost, enter your price per foot for each size, then switch the material and look at the wire total.
What is the voltage drop formula for three phase?
VD = √3 × K × I × L ÷ CM, where K is 12.9 for copper or 21.2 for aluminum, I is the line current, L is the one-way length in feet and CM is the conductor’s area in circular mils. Single phase uses 2 in place of √3 (1.732), so the same current on the same wire drops about 13% less on three phase. For example, 100 A at 208 V three phase over 200 ft of 1/0 copper drops 4.23 V, 2.04%. On a single-phase circuit the same current would drop 2.35%. The formula assumes a balanced load.
Why do other voltage drop calculators give slightly different answers?
They use different resistance values. This one uses the K method: DC resistance per circular-mil foot at 75 °C. Others use the resistance per 1,000 ft from the NEC Chapter 9 tables, or AC impedance with a power factor, and those give slightly different answers. The K method ignores reactance and power factor. That is close on 1/0 AWG and smaller. At 2/0 and up, most of all in steel conduit, the real drop can be higher than the K method shows, so check large feeders with AC impedance and the load’s power factor.
Are my measurements and prices sent to BuildWorkPro?
The calculator sends nothing: the math runs in your browser, and your wire prices and your estimate are saved in this browser’s local storage, never on our servers. The circuit details are kept in the page address so you can bookmark or share a result; like any page address, it is recorded by our site analytics if you accept analytics cookies.